Key takeaways
- Solar panel wire size comes from NEC 2023 690.8. Maximum circuit current is 125 percent of module Isc, and the conductor must carry 125 percent of that, which is 156 percent of Isc, before any derating.
- There are two checks and the larger answer wins: 125 percent of maximum current at the terminal temperature rating, and maximum current after temperature correction and conduit fill adjustment.
- NEC 2023 310.15(B)(2) adds 33 °C to the design temperature for raceways less than 3/4 inch above a roof. NEC 2017 and 2020 set the line at 7/8 inch.
- The same string can need #12 copper in raised conduit and #8 in conduit lying on the roof.
- Voltage drop is not an NEC requirement for PV, but inverter makers set their own limits, and Enphase recommends under 2 percent on the AC side of its microinverters.
Solar panel wire size is set by NEC 2023 690.8, not by a chart. Calculate the circuit’s maximum current from module short-circuit current, then size the conductor to pass two checks: 125 percent of that current at the terminal rating, and the full current after temperature and conduit fill corrections. Then check voltage drop. Below is each step, with a worked rooftop example.

How do you size solar panel wire?
Size solar panel wire in four steps: find the circuit’s maximum current under NEC 2023 690.8(A), check 125 percent of it against the terminal-rated ampacity under 690.8(B)(1), check the full current against the corrected and adjusted ampacity under 690.8(B)(2), and take the larger conductor. Then confirm voltage drop is acceptable.
- Maximum current, 690.8(A). For a PV source circuit, the sum of the short-circuit currents of modules in parallel, times 1.25. For an inverter output circuit, the inverter’s continuous output current rating.
- Terminal check, 690.8(B)(1). The conductor’s ampacity in the column matching the lowest terminal temperature rating, usually 75 °C under NEC 2023 110.14(C), must be at least 125 percent of the maximum current. No derating applies in this check.
- Conditions-of-use check, 690.8(B)(2). The conductor’s ampacity in its insulation column, 90 °C for PV wire and THWN-2, after ambient temperature correction and adjustment for more than three current-carrying conductors, must be at least the maximum current.
- Voltage drop. Upsize if the run is long enough to waste energy or push an inverter toward its voltage trip.
On Avila Solar Drafting’s solar plan sets, those calculations sit in the conductor schedule beside the single-line diagram, because permit offices expect to see the work. The County of Riverside, California PV permitting guidelines, for example, require conductor size and type on the single line diagram and list missing conductor sizes among their typical plan check comments.
Why is solar wire sized at 156 percent of Isc?
Solar source circuit wire is sized at 156 percent of module short-circuit current because NEC 690.8 applies 125 percent twice: once in 690.8(A) for irradiance above the module’s rating condition, and once in 690.8(B)(1) because PV current is continuous. 1.25 × 1.25 = 1.5625.
Module short-circuit current is measured at 1,000 W/m². Real irradiance exceeds that on clear, cold days and at the edge of clouds, so the first 125 percent covers the extra current. The second treats the circuit like any other continuous load. Penn State’s AE 868 PV design course walks through the same two factors.
The module’s Isc comes from the same datasheet used for solar string sizing, and strings in parallel add their currents before the first 125 percent is applied.
How does heat change solar wire size?
Heat lowers a conductor’s allowable ampacity, so a hot site or a raceway lying on the roof can force a larger wire. The correction factor comes from NEC 2023 Table 310.15(B)(1)(1), and conduit less than 3/4 inch above the roof gets 33 °C added to the design temperature first.
| Design temperature | Correction factor, 90 °C conductor |
|---|---|
| 31 to 35 °C (87 to 95 °F) | 0.96 |
| 36 to 40 °C (96 to 104 °F) | 0.91 |
| 41 to 45 °C (105 to 113 °F) | 0.87 |
| 46 to 50 °C (114 to 122 °F) | 0.82 |
| 66 to 70 °C (151 to 158 °F) | 0.58 |
| 71 to 75 °C (159 to 167 °F) | 0.50 |
The rooftop threshold changed in the current cycle. The Steel Tube Institute’s summary of 2023 NEC changes notes that NEC 2023 requires raceways in sunlight to sit at least 3/4 inch above the roof to avoid the 60 °F adder, where earlier editions said 7/8 inch. Type XHHW-2 conductors are exempt. Which number applies depends on the edition your AHJ enforces, and our walkthrough on finding your AHJ’s NEC cycle shows how to confirm it.
Use a recognized design temperature, not a guess. The NEC’s informational note points to the ASHRAE Handbook, Fundamentals, which publishes design temperatures by weather station.
Worked example: two strings in rooftop conduit
Two strings of modules with a 13.9 A short-circuit current, run together in one conduit at a 38 °C design temperature, pass the ampacity checks on #12 copper when the conduit is raised at least 3/4 inch off the roof. With the conduit lying on the roof, the 33 °C adder fails both #12 and #10, and the run needs #8.
Maximum current per string is 13.9 A × 1.25 = 17.4 A. The terminal check needs 1.25 × 17.4 = 21.7 A at 75 °C. Two strings in one conduit means four current-carrying conductors, an 80 percent adjustment.
| Conductor | Terminal check, 75 °C (needs 21.7 A) | Raised conduit: 90 °C × 0.91 × 0.80 (needs 17.4 A) | Conduit on roof: 90 °C × 0.50 × 0.80 (needs 17.4 A) |
|---|---|---|---|
| #12 Cu | 25 A: passes | 30 × 0.91 × 0.80 = 21.8 A: passes | 30 × 0.50 × 0.80 = 12.0 A: fails |
| #10 Cu | 35 A: passes | 40 × 0.91 × 0.80 = 29.1 A: passes | 40 × 0.50 × 0.80 = 16.0 A: fails |
| #8 Cu | 50 A: passes | 55 × 0.91 × 0.80 = 40.0 A: passes | 55 × 0.50 × 0.80 = 22.0 A: passes |
Ampacity is not the last word on #12. If the strings need overcurrent protection, NEC 2023 690.9(B) sizes the fuse at 125 percent of 17.4 A, which rounds up to 25 A, and 240.4(D) limits #12 copper to a 20 A device. In that case #10 is the practical minimum even in raised conduit.
On the AC side, a 7.6 kW inverter rated at 32 A of continuous output needs 1.25 × 32 A = 40 A at 75 °C. #10 copper, at 35 A, fails; #8 copper, at 50 A, passes, on a 40 A breaker. That breaker is the one the 120% rule for solar checks against the busbar, and the inverter choice itself is covered in our post on the DC-to-AC ratio.
Does the NEC set a voltage drop limit for solar?
No. The NEC’s 3 percent and 5 percent voltage drop figures for branch circuits and feeders are informational notes, not requirements, and they do not address PV circuits specifically. The practical limits come from inverter manufacturers and from the energy lost in long runs.
On the AC side, a grid-tied inverter raises the voltage at its terminals to push current to the grid, so a long, undersized run can drive it toward its high-voltage trip. Enphase’s IQ8 installation manual recommends keeping total voltage rise under 2 percent from the start of the microinverter branch circuit to the breaker in the load center.
Voltage drop on a single-phase circuit is 2 × one-way length × current × resistance per foot. For the 32 A inverter above on a 100 foot run, using NEC Chapter 9 Table 8 resistance values for stranded copper:
| Conductor | Resistance (Ω per 1,000 ft) | Voltage drop | Percent at 240 V |
|---|---|---|---|
| #8 Cu | 0.778 | 2 × 100 × 32 × 0.000778 = 4.98 V | 2.1% |
| #6 Cu | 0.491 | 2 × 100 × 32 × 0.000491 = 3.14 V | 1.3% |
Both conductors pass ampacity; only #6 keeps this run under 2 percent. Equipment grounding conductors follow their own sizing rules, covered in our guide to solar grounding and bonding.
What do plan reviewers look for in the conductor schedule?
Plan reviewers look for a conductor schedule that shows, for every circuit, the conductor size and type, its insulation rating, the raceway, the number of current-carrying conductors, the design temperature used, the correction and adjustment factors, the resulting ampacity and the overcurrent device.
A schedule that shows only wire sizes leaves the reviewer to redo the math, and a design temperature with no source is an easy correction comment. The schedule is one of the sheets described in what’s included in a permit-ready solar plan set. For jobs that only need the electrical and permit drawings, our solar permit design service delivers the same calculations.
Frequently asked questions
What size wire do I need for solar panels?
For a single string of modules with a short-circuit current near 14 A, #12 or #10 copper usually passes both NEC 2023 690.8 ampacity checks in free air or in conduit raised off the roof. Conduit lying on the roof with several circuits in it can push the same string to #8. Run both checks with your module’s actual Isc and your site’s design temperature.
Why do solar wires need to carry 156 percent of Isc?
Solar circuit conductors carry 156 percent of module short-circuit current because NEC 690.8 applies 125 percent twice. The first 125 percent, in 690.8(A), allows for irradiance above the 1,000 W/m² rating condition. The second, in 690.8(B)(1), treats PV current as continuous. 1.25 × 1.25 = 1.5625.
What is the rooftop temperature adder in the 2023 NEC?
Under NEC 2023 310.15(B)(2), a raceway or cable exposed to sunlight less than 3/4 inch above a roof gets 33 °C (60 °F) added to the outdoor design temperature before the correction factor is applied. NEC 2017 and 2020 used a 7/8 inch threshold. Type XHHW-2 conductors are exempt from the adder.
What is the maximum voltage drop for a solar system?
The NEC sets no mandatory voltage drop limit for PV circuits; its 3 and 5 percent figures for branch circuits and feeders are informational notes. Microinverter manufacturers publish their own limits, and Enphase’s IQ8 installation manual recommends keeping total voltage rise under 2 percent from the start of the branch circuit to the breaker.
Can THWN-2 be used for solar wiring?
THWN-2 is a common choice for PV circuits inside a raceway. Exposed single conductors in the array, such as module leads and jumpers, are normally PV wire or USE-2 under NEC 2023 690.31. For the ampacity math, both are 90 °C conductors, so the 90 °C column applies to the conditions-of-use check.
If conductor sizing or voltage drop keeps coming back as a correction comment, send us the site, the equipment and the run lengths. Avila Solar Drafting delivers standard residential solar plan sets in 2 to 3 business days, with AHJ and utility revisions free with no time limit and client change orders free for 3 months from data submission.